jessea1015
Post subject:air through elbows PostPosted: Sep 05, 2004 - 07:57 PM #1588



Joined: Jun 27, 2003
Posts: 7
Location: Columbia, MO
We have a chart at my shop that tells how many feet different kinds of fittings are worth. It says an elbow with a square heel and throat has the same amount of air loss as an elbow w/ a radius heel and square throat.Is this true? Excuse me if my lingo is not correct.
View user's profile Send private message
Reply with quote Back to top
CadMan
Post subject:RE: air through elbows PostPosted: Sep 09, 2004 - 04:08 PM #1595



Joined: Sep 01, 2004
Posts: 10
Location: Texas
I read thru the SMACNA Duct Design book and all I found was that a radius throat is about 70% better airflow than a standard 90. Couldn't find anything about the heel though. I was interested in where you got this chart and where I might get one.
View user's profile Send private message
Reply with quote Back to top
tazman
Post subject:RE: air through elbows PostPosted: Sep 09, 2004 - 09:36 PM #1596



Joined: Aug 29, 2004
Posts: 4
Location: The Netherlands
Radius is always better then square, when it is about the air resistance.
We ALWAYS use elbows with a radius. Except for the inner radius, when there is too less space we use square.

I have a simple mind and see it simple. Air likes a quiet easy ride, and not a ductsystem like rollercoaster!
Also watch out for noises!!! I never here about sound in here. There are some golden rules.
One of them is sharp edges, they can cause some noise.
View user's profile Send private message
Reply with quote Back to top
bordontn
Post subject:RE: air through elbows PostPosted: Oct 20, 2004 - 09:52 PM #1755
Power User
Power User


Joined: Sep 16, 2003
Posts: 213
Location: McEwen, TN.
Be careful of those square throats on a radius elbow....I'm posting part of a chart which shows the resistance in feet of duct..
the itinerant tinker a.k.a. bordontn
View user's profile Send private message Visit poster's website
Reply with quote Back to top
Gate
Post subject:RE: air through elbows PostPosted: Oct 28, 2004 - 12:26 AM #1783



Joined: May 02, 2004
Posts: 8
Location: Ohio, USA
A vaned square throat/heel ell is better for airflow than a radius heel with square throat. If you vane this configuration you need to run full vanes evenly spaced...

peace,
- Gate
View user's profile Send private message
Reply with quote Back to top
energystar
Post subject:RE: air through elbows PostPosted: Mar 05, 2008 - 04:25 PM #7317



Joined: Mar 05, 2008
Posts: 5

I was told by an engineer that a radius throat with a square heal is the way to go. It's better than a sq/sq with no vanes
View user's profile Send private message
Reply with quote Back to top
Bud
Post subject:RE: air through elbows PostPosted: Mar 05, 2008 - 10:36 PM #7319
Webmaster
Webmaster


Joined: May 13, 2003
Posts: 1308
Location: Waukesha
Better then vanes? I don't think so. The radius throat and heel is great way to fab elbows, and you really want to learn more about the radius to width ratio for maximum air flow or air flow with the least resistance. If you can't use a radius throat, you should probably consider vanes to help the air flow around the corner.

_________________
"If you make your job important it is quite likely to return the favor" Author Unknown
View user's profile Send private message Send e-mail Visit poster's website AIM Address
Reply with quote Back to top
legacy
Post subject:RE: air through elbows PostPosted: Mar 06, 2008 - 02:53 AM #7322



Joined: Oct 01, 2006
Posts: 44

We once had a guest speak at a union/management committee day, he was representative from the ITI (body that governs all SMWIA apprenticeship programs). ...Anyway, he was retiring from the ITI and was moving from CA to TN and was having a house built. On one of his final trips to check on construction, he noticed that the HVAC constractor had used all srare throat/ radius heel 90's. He made the take them out and replace them with full (1-1/2X) radius 90's where they would fit and sqaur with vanes where they did not.

I have made sq throat/radius heel for people that have walked into my shop looking for duct, but have never made that fitting for one of my jobs.

Just like a point to point (no miter) offset, if you measure the distance from the inside of a square throat to the mid point of the radius heel of a sq/rad 90, its got to choked down by at leats 10%-15% I would think.
View user's profile Send private message
Reply with quote Back to top